Ship lighting system insulation fault finding practical training operation
I. Operational content
- (1) Analog operating lighting circuit 220 V grid insulation low alarm;
- (2) Operation of the pull-power search method;
- (3) A hand-operated megohmmeter to test the insulation of the power grid.
II. Practical steps
Answer alarms, silencing, and flashing.
Observe the reading of the distribution board megohmmeter to see if the reading is less than 1 MΩ, if so, then the grid insulation failure, otherwise you can pull the power to find or energized to find the way to find out the insulation performance of the part of the equipment.
(3) The proper operation of the pull-power search method:
① Switch observation:Disconnect the power switches one by one, observing the megohmmeter while disconnecting the switches. If you disconnect a switch, the insulation is back to normal, it shows that the switch controlled by the electrical equipment insulation is not good. Then the other disconnected switches one by one, while observing the megohmmeter readings, if the readings become smaller after the closure, then the circuit insulation is not good.
② Disconnect the power supply:Upon discovery of a ground fault line power supply switch, cut off the power supply to that line.
③ Secondary search:Use a hand-operated megohmmeter (commonly known as: a rocking meter) at the distribution panel (if present) to locate the secondary distribution network. Measure the insulation condition of the branch circuits to ground one by one.
④ Restore power supply:After locating the grounded branch circuit, pull off this distribution switch, close the rest of the switches, and close this distribution switch in front of the main switchboard to supply power to the rest of the equipment.
(4) The proper use of a hand-operated megohmmeter:
① Confirmation of good and bad:
- A. Open circuit test:120 r/min speed shaking megohmmeter, two pens open circuit, megohmmeter pointer points to “∞”.
- B. Short circuit test:Gently turn the handle, two pens short circuit, megohmmeter pointer points to “0”.
② Find the grounding point:In the case of a lighting system, when looking for a specific grounding point, you can use the(Maoism) one divides intwoThe grounding is done by disconnecting from the intermediate junction box to measure and determine which small area is grounded. After that, there are only a limited number of power supply points in each small area, and each power supply point should be checked one by one, mainly checking part of the leads of lamps, plugs and switches, and checking the internal conditions of lamps, plugs and switches. If no grounding point can be found after these checks, the cable from the junction box to the appliance should be checked until a grounding point is found.
III. Analysis and treatment of single-phase faults in lighting systems
Set the point of failure:Ground the kitchen light phase A in the lighting grid.
Phenomenal manifestations:
“AC 220V BUS LOW INSUL.” lamp flashes and the buzzer alarms as shown in Figure 7-5.
ANALYSIS: The light indicates low insulation of the lighting grid.
Figure 7-5 220V Low Insulation Fault Alarm
Treatment:Silence the sound and flash, acknowledge the alarm, as shown in Figure 7-6, use the pull method to locate the secondary network where the insulation fault occurred, and then use a hand-operated megohmmeter to locate the specific grounding point.
Figure 7-6 Alarm Handling Buttons
SOP (Sequential Operating Procedures)
















